![GE Digital Energy Kelman MINITRANS Скачать руководство пользователя страница 68](http://html.mh-extra.com/html/ge-digital-energy/kelman-minitrans/kelman-minitrans_installation-manual_571855068.webp)
MA-005 - MINITRANS Installation Manual - Rev 3.1
29-Sep-15
Page 68 of 85
M.1.3
Visual inspection
Inspect all six isolators at the following times:
In situ before and after preparation for transit.
In situ before and after relocation / installation at each new site.
Each inspection shall look for the following signs:
Defects on the silicone.
Peeling of silicone from the metal portion.
Corrosion on the metal portion of the isolator.
Corrosion or signs of structural compromise on the metal work / brackets.
Figure M—1: Isolator
M.1.4
Checks and measurements
Isolator Alignment
: Inspect all six isolators to ensure proper alignment. If
required, unscrew the nuts and adjust the isolators so that the opposing
threaded portions of each isolator are aligned.
Measure skew distance
: Report any skew which is greater than 4 mm (measured
from bolt centre to bolt centre as shown in Figure M—2).
Note: Use a measurement
tool, such as a ruler, calipers or similar.
Ensure proper alignment.
Figure M—2: Misalignment and skew distance
Silicone:
Look for defects
Silicone / Metal
boundary:
Look for peeling
Metal portion:
Look for corrosion
Minimise the skew
distance and report
if over 4 mm.