![GE Digital Energy Kelman MINITRANS Скачать руководство пользователя страница 67](http://html.mh-extra.com/html/ge-digital-energy/kelman-minitrans/kelman-minitrans_installation-manual_571855067.webp)
MA-005 - MINITRANS Installation Manual - Rev 3.1
29-Sep-15
Page 67 of 85
Direct Mount Cradle Locking Mechanism
Appendix M
Introduction
M.1
M.1.1
Purpose and scope
This appendix details how to use the Locking Mechanism on a Direct Mount Cradle-
installed MINITRANS so as to prepare a transformer for transit. Typically this occurs in the
following scenarios:
On a mobile transformer (one that is moved from site to site).
On any transformer where a MINITRANS is pre-installed prior to shipping.
But equally applies to any scenario where there is a requirement to move or relocate a
transformer with a pre-installed MINITRANS.
The appendix details how to install and uninstall the following locks:
Exterior cradle transit lock
Interior mini PGA transit lock
M.1.2
Safety considerations
It is important to follow the procedures defined in this document to maintain the
warranty and avoid:
A safety risk during installation, operation and transit.
Impaired functionality, since increased noise to the sensor would invalidate the
readings as noise test results are logged for every measurement.
The primary earth must be installed
. Since the silicone isolators provide a
degree of electrical isolation from Ground, the importance of installing the
primary earth increases (see Section 9).
Ensure that when accessing the interior of the enclosure that the mains
electrical supply is isolated before the enclosure door is opened. Follow the site
lock out-tag out (LOTO) procedure.
Note: the product may have more than one electrical
supply.