![GE Digital Energy Kelman MINITRANS Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/ge-digital-energy/kelman-minitrans/kelman-minitrans_installation-manual_571855033.webp)
MA-005 - MINITRANS Installation Manual - Rev 3.1
29-Sep-15
Page 33 of 85
10.3
Accessory Power
There are additional power points to c12 V DC or +24 V DC at 0.5 A accessories,
such as wireless modems or protocol converters. These are available on the Input board
at the front of the product as shown in Figure 10—1).
Figure 10—1: Accessory power points for 12 V and 24 V
10.4
External Sensors
A transformer load sensor is provided in the product installation kit to measure and
record the transformer load. The transformer load sensor is a split core current sensor
that can be installed unobtrusively around a CT line receiving a feed from the main
bushing secondary wiring (usually located within the marshalling / control cabinet of the
transformer).
It should be possible to locate a suitable current transformer with a 0 A – 5 A secondary
circuit on which to mount the sensor. The sensor is supplied with 2.5 m (100 in.) of cable
and may be spliced to the required length to connect to the product with up to a total of
10 m (33 ft) of 20 AWG twisted pair cable. Longer cable lengths are possible depending
upon the quality of the cable. The load sensor connects to terminals 25 and 26 on the
bottom right-hand side of the Input board (see Appendix I).