Checks and Measurements
L.6
Isolator Alignment
: Inspect all six isolators to ensure proper alignment. If required,
unscrew the nuts and adjust the isolators so that the opposing threaded portions of
each isolator are aligned.
Measure skew distance
: Report any skew which is greater than 4 mm (measured
from bolt centre to bolt centre) as shown in Figure L—18.
Note: Use a measurement tool,
such as a ruler, calipers or similar.
Ensure proper alignment.
Figure L—18: Misalignment and skew distance
Compression check
: Measure the distance of compression on all six isolators and
ensure
that it is less than 21 mm as shown in Figure L—19. If it is greater than this
value, the isolator will be in tension and will likely fail. Contact the Customer Service
Centre.
Use only in compression.
Figure L—19: Isolators used in compression and compression distance
Must be 21 mm or less.
Minimise the skew
distance and report
if over 4 mm.