54
ENTRA
EB
Parameters list:
ID
PARAMETER
SETTING
DEFAULT
01
Opening speed
RANGE:
20°/s ÷ 70°/s
(step of 5°/s)
60
02
Closing speed
RANGE:
10°/s ÷ 40°/s
(step of 5°/s)
20
03
Idle time
RANGE:
0 ÷ 60 seconds (step of 1s);
62: 2 min.
63: 3 min.
64: 4 min.
0
04
Idle time in Low
Energy
RANGE:
5 ÷ 60 seconds (step of 1s);
62: 2 min.
63: 3 min.
64: 4 min.
5
05
With SPRING
Closing speed with
spring power
assisted
RANGE:
1 ÷ 9
(1=minimum speed, 9=maximum speed)
5
With MOTOR only
Level anti-wind
RANGE:
0 ÷ 9
(0=disabled, 1=Minimum level, 9=Maximum level)
0
06
Anti-crushing
RANGE:
1 ÷ 9 both opening both closing
(1=più sensibile; 9=meno sensibile)
5
07
Acceleration
RANGE:
5 ÷ 30
(step of 1) Modify both acceleration and deceleration
30
08
Approaching angle
RANGE:
10° ÷ 40°
(it modifies both parameters (closing 1/2 of the opening)
20
09
Electric lock power
0 = 12 VDC
1 = 24 VDC
0
10
Lock type
0 = Lock not used
For different type of electric locks please refer to paragraph
“electric locks setting”
0