64
ENTRA
EB
Set on MASTER and SLAVE control boards the following values:
ID
DESCRIPTION
SETTING
DEFAULT
13
Mode
Single/Double
0 = Single
1 = Double Master
–
wiring on terminal board
2 = Double Slave
–
wiring on terminal board
3 = Double Master
–
wiring CAN cable
4 = Double Slave
–
wiring CAN cable
0
Depending on whether you need to have an offset in the doors, set the following values:
•
Synchronized doors on MASTER control board parameter 21=0 and 22=0 (valid for option B)
•
NON-Synchronized doors on MASTER control board parameter 21>0 and 22>0 (valid for options A e BD)
OPERATION
DESCRIPTION
Electric-lock
Managing is allowed (with relative logic) on both control boards as in the case of
single operators.
Push & Go
Activatable on both control boards in the same way as a single operator.
Detecting the attempt to open a door causes the opening of both doors.
Anti-crushing
Value separately and independently managed from both control boards.
•
If one board detects an anti-crushing in closing, the movement of both
doors stop and they slowly go in complete opening position.
•
If one board detects an anti-crushing in opening, the movement of the
door that detects the anti-crushing stop and bring the door slowly in
closing position. Other door, meanwhile will have reached the opening
position, it will wait the other door before starting the closing cycle.
ATTENTION:
•
Both operators must use the same main power supply exit.
•
Do not use any switches or fuses in between the two operators.
•
Optional external peripherals (KEY, START 1 e START 2), must be connected only on MASTER.
•
Safety sensors (SAFE OPEN e SAFE CLOSE) must be connected separately on both control boards.
•
Selector (optional) must be connected only on MASTER. In case of setting parameters with selector,
they will be learned on both MASTER and SLAVE control boards
•
Commissioning must be set only on MASTER
•
During
“
LP
”
MASTER door will be the first to move, and it must be stopped at desired position to
give a door limit.
Immediately after SLAVE door will start moving and it also must be stopped at desired position to give a
door limit. When
“
LP
”
will finish both doors will go in STOP close position (on display
“
CL
”
fix). A carter kit is
available as optional, an extension base plate and cover to join two operators.
ID
DESCRIPTION
SETTING
DEFAULT
21
Displacement in
opening for double
RANGE: 0 ÷ 100
Displacement in opening by step of 100ms (
“
0
“ if
synchronized)
0
22
Displacement in
closing for double
RANGE: 0 ÷ 100
Displacement in closing by step of 100ms (
“0“ if
synchronized )
0
Содержание ENTRA EB