M
CB
3
Installation Manual
Page 48
Code
Description
10401
LH Raise Driver Overload. Valve Conn. Pin B
If Current Exceeds 5 Amps driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
LH drivers stay off until power is cycled.
10402
LH Lower Driver Overload. Valve Conn. Pin A
If Current Exceeds 5 Amps driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
LH drivers stay off until power is cycled.
10403
RH Raise Driver Overload. Valve Conn. Pin F
If Current Exceeds 5 Amps driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
RH drivers stay off until power is cycled.
10404
RH Lower Driver Overload. Valve Conn. Pin G
If Current Exceeds 5 Amps driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
RH drivers stay off until power is cycled.
10405
LH/AUX Driver Overload. Valve Conn. Pin C
If Current Exceeds 5 Amps driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
driver stays off until power is cycled.
10406
RH/AUX Driver Overload. Valve Conn. Pin D
If Current Exceeds 5 Amps driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
driver stays off until power is cycled.
10407
LH PV Driver Overload. Valve Conn Pin E
If Current Exceeds 6 mA driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
driver stays off until power is cycled.
10408
RH PV Driver Overload. Valve Conn Pin H
If Current Exceeds 6 mA driver turns off for 250ms. If 3 shut offs in 5.0 sec.,
driver stays off until power is cycled.
10409
LH Receiver Overload. Receiver Conn Pin A
If Current Exceeds 6.5A driver turns off .
10410
RH Receiver Overload. Receiver Conn Pin G
If Current Exceeds 6.5A driver turns off .
10510
LH PV Fault, Danfoss Valve; PV signal exceeds 15-85% of Mach Volt,
LVDT wires Broken, Spool position exceeds command.
Fault will clear when fault removed and power cycled.
10511
RH PV Fault, Danfoss Valve; PV signal exceeds 15-85% of Mach Volt,
LVDT wires Broken, Spool position exceeds command.
Fault will clear when fault removed and power cycled.
10604
Machine Volts High, Machine Voltage greater than 31.5 volts.
10605
Machine Volts Low, Machine Voltage less than 9.5 volts.
1505
Momentary lapse of communication with the laser receiver(s). Usually occurs due to low
power during engine cranking. Cycling Power re-establishes communication.
10501
Default Values Loaded - Occurs when updating software (V1.00 to V2.00) due to
parameter memory location changes.
APPENDIX B
Fault Codes
Fault code messages may be cleared by activating either multi-switch
Содержание MCB3
Страница 1: ...MCB3 CONTROL BOX Installation Manual Technical Information Software Version 3 00 P N ATI 026046 Rev C...
Страница 57: ...MCB3 Installation Manual Page 55 NOTES...
Страница 58: ...MCB3 Installation Manual Page 56 NOTES...
Страница 59: ...Page 57 NOTES MCB3 Installation Manual...
Страница 60: ...Futtura Tools Technologies Inc 100 N Rockwell Ste 96 Oklahoma City OK 73127 USA...