Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
43
COMMISSIONING
Fire alarm with output delays
The system can be programmed with delays to outputs (fire alarm sounders). If a delay has been
programmed this is indicated by the DELAY LED which will be illuminated. Delays can be applied to
all zones or individual zones as required.
A programmed delay can be turned off if required in the menu option 11: Set delays.
If a delay is turned ‘OFF’ DELAYS INACTIVE will be displayed alternately on the normal display. If
the delay is set ‘ON’ the DELAY LED will be illuminated.
If the acknowledgement and investigation delay option is enabled. A fire alarm is registered at the
panel but does not immediately activate the sounders or remote output (dependant on program
settings). The display will show:-
[FIRE /DELAY 019 ZONE 01 OF 01 ZONES ACK TIME]
[40 CHARACTERS LOCATION TEXT]
The delay timer shows how much time is left for acknowledgement. If the alarm is not acknowl-
edged before the first timer expires the panel will enter full alarm
The alarm can be acknowledged by pressing button [5] on the keypad. If the sounders are active
they may be silenced by pressing SILENCE / RESOUND ALARMS button.
Once acknowledged the display will show:-
[FIRE /DELAY 120 ZONE 01 OF 01 ZONES INVEST]
[40 CHARACTERS LOCATION TEXT]
The delay timer shows how much time is left for investigation. If the alarm is not RESET before the
second timer expires the panel will enter full alarm..
Pressing EVACUATE or operating a manual call point will terminate the investigation delays and
activate all programmed sounders.
IMPORTANT
The Fusion panel large box (FBULxx-xx-xx) has a clear acrylic window protecting the display and
controls. If investigation delays are used, a manual call point must be mounted near to the panel to
enable instant override of the delay at access level 1, to ensure EN54-2 compliance.
The investigation timer can be disabled in the Set Delays menu. Note:- When the investigation
alarms are disabled. Sounders will activate immediately following a detector alarm.
Содержание FBUL NP12-12
Страница 2: ......
Страница 27: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 27 LOOP PCB PCFSB11 Loop Card...
Страница 35: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 35...
Страница 45: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 45...
Страница 87: ......
Страница 88: ......