Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
71
CONFIGURATION (continued)
Device configuration
Device types
Generic types are used for setting the expected type for programming purposes. The panel will use
the specific device type code found and deal with the device according to its requirements as de-
tailed below:
OPT
(optical types)
ION
(ionisation types)
These devices have only one associated text message & zone allocation. If the device is Discovery
protocol, a sensitivity setting can apply. The default settings for this type are: - blank text, unassigned
for zone, sensitivity mid range , non silent mode, no group allocations, no base type set.
Part Number
Type
Sensitivity
Input
attribute
55000-600 XP95
Optical
n/a
[s]
55000-885
XP95 Multi sensor
n/a
[s]
58000-600 Discovery
Optical
1-5
[s]
58000-700
Discovery Multi sensor
1-5
[s]
55000-268
XP95 5-50M beam
n/a
[s]
55000-273
XP95 10-100M beam
n/a
[s]
55000-028/9 Flame
detectors
n/a
[s]
Part Number
Type
Sensitivity
Input
attribute
55000-500 XP95
ionization
n/a
[s]
58000-500 Discovery
ionization 1-5
[s]
58000-300
Discovery C0 detector
1-5
[s]
Содержание FBUL NP12-12
Страница 2: ......
Страница 27: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 27 LOOP PCB PCFSB11 Loop Card...
Страница 35: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 35...
Страница 45: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 45...
Страница 87: ......
Страница 88: ......