Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
77
CONFIGURATION (continued)
Set panel parameters
1) Edit company name
A 40 character display message can be set here using the text entry template on the keypad.
Press menu to exit.
2) Edit panel name
A 14 character name may be given to the panel for identity purposes. Use text entry template
to edit. Press menu to exit.
3) Set number of remote panels
In a network system, the quantity of other panels must be entered to all panels, for integrity
monitoring purposes. Use scroll buttons to edit the quantity. Press menu to exit.
Set power supply type
Is the standard Fusion power supply being used or an alternative? Unticking this box removes the
standard data based monitoring function of the power supply input and converts the PSD and PSC
inputs into switched negative battery and charger fault inputs from alternative power supplies.
Set ‘common’ response mode
Scroll
[2]
&
[8]
to edit
1) Local panel only
2) System-wide
In a network system, this setting determines if ‘common’ as applied to output device responses, is
restricted to the local panel or activated from all panels in the network.
Set keypad options
This option specifies, in a network, if this panel has the ability to silence and/or reset alarms on other
panels. If set to YES then the silence and/or reset will only function if there is an alarm locally. If set
to NO then the panel can silence or reset any alarm on any panel. This is to provide the possibility of
providing a silence or reset command from an originating panel only.
LOCAL EVACUATE, SILENCE and RESET buttons.
When set to ‘NO’ the buttons operate system wide.
When set to ‘YES’ buttons operate locally only
Set number of boards
Set quantity of boards expected in the panel. An incorrect quantity will show a panel fault.
The menu also offers a ‘yes’ or ‘no’ setting for the presence of an extension LED zone indicator PCB
(zones 17-64). Set to ‘yes’ if this is fitted.
Содержание FBUL NP12-12
Страница 2: ......
Страница 27: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 27 LOOP PCB PCFSB11 Loop Card...
Страница 35: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 35...
Страница 45: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 45...
Страница 87: ......
Страница 88: ......