Fusion Installation & Commissioning Manual Approved document No UI-FBU-01 issue 3.0
36
PANEL SET UP AND INITIALISATION
As delivered from the factory the control panel will be supplied completely set up and no initialisation
will be required.
The addition of expansion boards will require changes to the configuration of the panel. This will in-
volve changes to the DIL switches and settings in the control panel parameters.
FSB17 Main Board DIL Switch Setup
12
3
4
5
6
7
ON
1
2
4
8
16
P
F
Panel
Switch
1
2
3
4
5
6
1
Address
0
0 0 0 0 x x
2
Address
1
1 0 0 0 x x
3
Address
2
0 1 0 0 x x
4
Address
3
1 1 0 0 x x
5
Address
4
0 0 1 0 x x
6
Address
5
1 0 1 0 x x
7
Address
6
0 1 1 0 x x
8 - 15
Address 7 etc
1
1
1
0
x
x
16
To address 15
1
1
1
1
x
x
P
Program
mode x x x x x 1
F
Flash
upgrade x x x x x 0
7
X
X
X
X
X
X
X
X
X
0
1
FSB10 BANK Address DIL Switch Setup
SWITCHES
1 - 4 = PANEL NETWORK ADDRESS
5 = NOT IN USE
6 = PROGRAM MODE (WRITE PROTECT)
7 = FLASH PROGRAM MODE
KEY
0 = OFF, 1 = ON, X = NOT USED
12
ON
BANK ADD
Bank
Switch
1
2
1 Address
0 0
0
2 Address
1 1
0
3 Address
2 0
1
4 Address
3 1
1
SWITCHES
1 - 2 = BOARD BANK ADDRESS
MAX 4 BANKS
N.B.
For BANK 1, the switches are no longer fitted
12
ON
1 2
AD
D
S3
Board
Switch
2
3
1 Address
0 0
0
2 Address
1 1
0
3 Address
2 0
1
4 Address
3 1
1
S3 BOARD ADDRESS SWITCH
1 & 2 BOARD ADDRESS MAX 4 BOARDS PER BANK
IMPORTANT
BANK/BOARD ADDRESS WILL SET LOOP/ZONE No
SEQUENCE BY ADDRESS ORDER
Set ‘ON’ when required
FSB11 Loop Card DIL Switch Setup
Содержание FBUL NP12-12
Страница 2: ......
Страница 27: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 27 LOOP PCB PCFSB11 Loop Card...
Страница 35: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 35...
Страница 45: ...Fusion Installation Commissioning Manual Approved document No UI FBU 01 issue 3 0 45...
Страница 87: ......
Страница 88: ......