Table A-9: Height requirement for the new lightning rod
LPL Condition
Height
[m]
I
7.4
II
5.5
III
4.5
IV
4.0
4. Protection of Structures Against Lightning
4.1. Old lightning and angle of protection standard
Old standard stated the protection angle of lightning rods for
protecting of people from lightning, electrical facilities, petroleum
complexes, gas tanks, plant, and equipment was 60º or less for
general buildings. Factory handling hazardous materials such as
explosives, flammable gas, liquids, and etc., would be slightly
narrower as 45º. Because these specifications were old they did not
take height in consideration. Also the protection area was too large
and therefore not safe enough even within the protection angle.
The basic data of this standard was created using results of an
experiment that tested using an artificial lightning generation
apparatus. Since the electrical discharge size generated was too
small when compared to actual lightning, it was found that the
experiment data results varied from actual lightning observation.
7.305 m
5.475 m
4.472 m
4.0 m
α
Figure A-5:
Protection range
α: Protected angle
Содержание 9ZWWR2120
Страница 1: ...S2E 17 0209_IM_WR2120_C i INSTALLATION MANUAL MODEL WEATHER RADAR TYPE WR2120 www furuno com...
Страница 44: ...S2E 17 0209_IM_WR2120_C 2 8 OUTLINE DRAWING 1 Antenna Unit...
Страница 45: ...S2E 17 0209_IM_WR2120_C 3 2 Signal Processing Unit Storage box...
Страница 46: ...S2E 17 0209_IM_WR2120_C 4 4 Data Processing Unit...
Страница 47: ...S2E 17 0209_IM_WR2120_C 5 5 Data Processing Unit DPU Power Supply...
Страница 49: ...S2E 17 0209_IM_WR2120_C 7 WR2120 Configuration...