S2E-17-0209_IM_WR2120_C
11
2.2.2. Assessment of annual number
of dangerous events
According to the statistic information provided by the National Environment Agency of Singapore,
average thunderstorm days per year (
) at Changi is 168. The lightning ground flash density
will be leaded as follows:
2.2.2.1. Number of dangerous events
for the structure
may be evaluated as the product:
where
is the lightning ground flash density
is the collection area of the structure
is the location factor of the structure, 0.5 for CWRP
1) Determination of the collection area
For isolated structures on flat ground, the collection area
is the area defined by the
intersection between the ground surface and a straight line with 1/3 slope which passes from
the upper parts of the structure (touching it there) and rotating around it. Determination of the
value of
will be performed graphically or mathematically.
For an isolated rectangular structure with length L, width W, and height H on flat ground, the
collection area is then equal to:
where L, W and H are expressed in meters.
Figure A-2: Collection area
of an isolated structure (IEC 62305-2)
2) Relative location of the structure
The relative location of the structure, compensating for surrounding structures or an exposed
location, will be taken into account by a location factor
. For the weather radar at CWRP,
(Structure surrounded by objects of the same height or smaller).
2.2.2.2. Assessment of the average annual number of dangerous events
due to flashes near a
structure
may be evaluated as the product:
where
is the lightning ground flash density
is the collection area of flashes striking near the structure
1:3
H
V
3H
L
IEC 2637/10
Содержание 9ZWWR2120
Страница 1: ...S2E 17 0209_IM_WR2120_C i INSTALLATION MANUAL MODEL WEATHER RADAR TYPE WR2120 www furuno com...
Страница 44: ...S2E 17 0209_IM_WR2120_C 2 8 OUTLINE DRAWING 1 Antenna Unit...
Страница 45: ...S2E 17 0209_IM_WR2120_C 3 2 Signal Processing Unit Storage box...
Страница 46: ...S2E 17 0209_IM_WR2120_C 4 4 Data Processing Unit...
Страница 47: ...S2E 17 0209_IM_WR2120_C 5 5 Data Processing Unit DPU Power Supply...
Страница 49: ...S2E 17 0209_IM_WR2120_C 7 WR2120 Configuration...