© Fulton Group N.A., Inc. 2022
MAINTENANCE & TROUBLESHOOTING
VSRT-IOM-2022-0728
SECTION 4
4-14
Problem
Cause
Remedy
Burner Cut-O
ff
Power Supply
Check fuse or circuit; reset or replace, as necessary.
Gas Supply
Check to be sure main gas cock is not closed. Check coil in gas
valve with OHM meter. Replace if faulty. Check gas regulator
setting and readjust as necessary. Check inlet gas pressure and
increase or decrease as necessary.
Ignition Electrodes
Check electrodes for carbon buildup and clean if necessary.
Check for proper adjustment. Readjust if necessary. Check for
cracks in porcelain; if found replace.
Air Switch
Use a volt meter in series with the air switch to check to see if
the switch is making (closing). Also check the adjustment of
the air switch setting. If both above do not work, check the
range of the air switch and measure the burner fan pressure at
the air pressure switch sensing port to make sure the air switch
is within range.
Dirty or defective UV Scanner
Clean or replace.
Water pump will
not come on at
times
Scale on probes
Check and clean or replace as necessary.
Bad pump contactor
Check to see if contactor is being powered. Check to see if
contactor coil is pulling in. Replace if necessary.
Bad pump motor
Check the incoming power to the pump to be sure it is
receiving power. If power is present but motor does not run,
replace it.
Low fuel pressure
Gas Pressure Regulator
Check and replace.
Boiler Flooding
Pump does not shut off
Dirty probes. Clean or replace as necessary.
Relay failed
Make sure relay is plugged in tightly. If so, replace water level
relay.
Ground Connection
Check for tightness and clean.
Vacuum created with boiler off
As the boiler cools off, it pulls water from the system piping.
To prevent this, add a 1/4” check valve on the steam gauge
assembly piping, which closes under pressure and opens
under vacuum.
Содержание VSRT Series
Страница 2: ......
Страница 84: ... FultonGroupN A 2022 OPERATION VSRT IOM 2022 0728 SECTION3 3 20 THIS PAGE LEFT INTENTIONALLY BLANK ...
Страница 102: ... FultonGroupN A Inc 2022 MAINTENANCE TROUBLESHOOTING VSRT IOM 2022 0728 SECTION4 4 18 PAGE LEFT INTENTIONALLY BLANK ...
Страница 115: ...Questions PleaseContactYourLocalManufacturer sRepresentative SECTION5 VSRT IOM 2022 0728 SERVICEDOCUMENTS 5 13 NOTES ...
Страница 116: ... FultonGroupN A 2022 SERVICEDOCUMENTS VSRT IOM 2022 0728 SECTION5 5 14 NOTES ...
Страница 117: ...Questions PleaseContactYourLocalManufacturer sRepresentative SECTION5 VSRT IOM 2022 0728 SERVICEDOCUMENTS 5 15 NOTES ...