Questions? Please Contact Your Local Manufacturer’s Representative
SECTION 4
VSRT-IOM-2022-0728
MAINTENANCE & TROUBLESHOOTING
4-15
Problem
Cause
Remedy
Poor Combustion
Damaged Refractory
Check refractories to see if they are plugged with soot or
broken in pieces. Clean or replace as necessary.
Not Enough Air/Build-Up on
Fan Wheel (
Rich; Burner Hums
)
Check CO2/O2 levels. If r
ich, disassemble filter housing and gas
train. Look inside inlet to the fan. If there is build-up on the fan
blades, clean fan. Recheck the CO2/O2 and adjust gas valve as
necessary for all combustion points.
Fuel Valve Adjusted Too High
(
Rich; Burner Hums
)
Check CO2/O2 levels. Check gas pressure at outlet of valve. If
the pressure is too high, make an adjustment at the valve. Be
sure to check all combustion points.
Fan Speed Too High
(Lean;
Unstable Flame)
Check fan discharge pressure. If too high, adjust fan speed.
Check CO2/O2 levels and adjust gas valve as necessary. Be sure
to check all combustion points.
Gas Valve Adjusted Too Low
(Lean; Unstable Flame)
Check CO2 and O2 levels. Check pressure at outlet of the valve.
If too negative, adjust gas valve as necessary.
Draft
Check draft with a gauge. Draft should be within the range
of -0.25” w.c. to + 1.50” w.c. May need to install a barometric
damper.
Dirty Flue
Check flue for carbon buildup or blockage. Clean flue passages
with brush.
Negative Room Pressure
Make sure no exhaust fans are running in the boiler room.
Burner back fires
Damaged Refractory
Check refractories to see if they are plugged with soot or
broken in pieces. Clean or replace as necessary.
Ignition Electrodes
Check electrodes for carbon buildup and clean if necessary.
Check for proper adjustment. Readjust if necessary. Check for
cracks in porcelain; if found replace.
UV Scanner
Check for debris on flame scanner and clean as needed. Check
for proper location of detector.
Draft
Check draft with a gauge. Draft should be within the range
of -0.25” w.c. to + 1.50” w.c. May need to install a barometric
damper.
Negative Room Pressure
Make sure no exhaust fans are running in the boiler room.
Содержание VSRT Series
Страница 2: ......
Страница 84: ... FultonGroupN A 2022 OPERATION VSRT IOM 2022 0728 SECTION3 3 20 THIS PAGE LEFT INTENTIONALLY BLANK ...
Страница 102: ... FultonGroupN A Inc 2022 MAINTENANCE TROUBLESHOOTING VSRT IOM 2022 0728 SECTION4 4 18 PAGE LEFT INTENTIONALLY BLANK ...
Страница 115: ...Questions PleaseContactYourLocalManufacturer sRepresentative SECTION5 VSRT IOM 2022 0728 SERVICEDOCUMENTS 5 13 NOTES ...
Страница 116: ... FultonGroupN A 2022 SERVICEDOCUMENTS VSRT IOM 2022 0728 SECTION5 5 14 NOTES ...
Страница 117: ...Questions PleaseContactYourLocalManufacturer sRepresentative SECTION5 VSRT IOM 2022 0728 SERVICEDOCUMENTS 5 15 NOTES ...