Page 48
MAINTENANCE - 5
5.4.2
LOW WATER LEVEL CHECK
5.4.3
EVAPORATION CHECK
This check may be required by your insurance inspector as part of the annual inspection.
To perform the evaporation check, follow the procedure in
Section 4.4.2 - Low Water Level
check
allowing water to lower by natural evaporation and
not
by manual blowdown.
1.
Ensure that the boiler is firing, the feedwater pump is not running and that the water level is
between Pump On and Pump Off.
2. Switch the Pump switch to the OFF position.
3. Allow the water level to lower by natural evaporation below the Low Water level.
Do not allow the water level to drop below the bottom of the water level gauge (sight glass).
4. Check:
a) Low Water limiter lights illuminate
b) Low Water audible alarm sounds
c)
Burner stops firing
d) Feedwater pump does not start
If the test fails, turn the boiler off and ensure that the fault is rectified before the boiler is
used.
5. Switch the pump switch to the ON position.
6. Check:
a)
Feedwater pump starts and refills the boiler
b) Water level rises above the Low Water level
c) Burner does not start
d) Low Water audible alarm continues to sound
7. Press the Common Alarm Reset switch for 2 seconds maximum
8. Check:
a) Low Water Limiter lights extinguish
b) Low Water audible alarm silences
c)
Burner automatic fire sequence starts
9. Verify that the pump continues to run until the Pump Off level is reached and then switches off.
Содержание VMP Series
Страница 8: ...VMP IOMM 2018 2 Fulton Ltd Page VIII...
Страница 25: ...VMP IOMM 2018 2 Fulton Ltd Page 17 INSTALLATION 2 Figure 10 Electrical Customer Terminal Connections...
Страница 30: ...VMP IOMM 2018 2 Fulton Ltd Page 22...
Страница 66: ...VMP IOMM 2018 2 Fulton Ltd Page 58...
Страница 100: ...VMP IOMM 2018 2 Fulton Ltd Page 92...
Страница 102: ...VMP IOMM 2018 2 Fulton Ltd Page 94 APPENDIX C...