TROUBLESHOOTING - 6
6.3
TROUBLESHOOTING
FEEDWATER PUMP
Problem
Cause
Remedy
8. Noise.
1. Cavitation occurs in the pump. Check the suction conditions.
2. Pump does not rotate freely
(frictional resistance because
of incorrect pump shaft
position.
Adjust the pump shaft.
3. Frequency converter operation. See Grundfos manual.
4. Boiler feedwater non-return
valve letting water passed
the valve seat, (normally
accompanied by banging in the
feedwater tank).
Check and clean boiler feedwater non-return valve, ensure
it is seating and not allowing water passed.
9. Water pump runs
intermittently
1. Scale on probes.
Check and clean probes, replace as necessary.
2. Faulty pump contactor
Check the contactor has power. Check the contactor is
pulling in.
Replace if necessary.
3. Faulty pump motor.
Check the pump has power.
If the pump has power but is not running, replace it.
4. Faulty Level Control Relay
Check the relay has power and is secure on it’s base.
Replace if faulty.
10.
Boiler flooding
1. Pump does not shut off.
Dirty probes. Clean or replace as necessary.
2. Relay failed.
Ensure the relay is secure on its base.
If so replace the water level relay.
3. Earth connection.
Clean and tighten as required.
4. Vacuum created with boiler
off.
As the boiler cools, it pulls water from the system piping.
To prevent this, add a check valve on the steam gauge
assembly piping, which closes under
pressure and opens under vacuum.
Содержание VMP Series
Страница 8: ...VMP IOMM 2018 2 Fulton Ltd Page VIII...
Страница 25: ...VMP IOMM 2018 2 Fulton Ltd Page 17 INSTALLATION 2 Figure 10 Electrical Customer Terminal Connections...
Страница 30: ...VMP IOMM 2018 2 Fulton Ltd Page 22...
Страница 66: ...VMP IOMM 2018 2 Fulton Ltd Page 58...
Страница 100: ...VMP IOMM 2018 2 Fulton Ltd Page 92...
Страница 102: ...VMP IOMM 2018 2 Fulton Ltd Page 94 APPENDIX C...