TROUBLESHOOTING - 6
CONTINUED ON NEXT PAGE
Problem
Cause
Remedy
3. Boiler fails to start
1. No Power
Check fuse or circuit breaker. Reset or replace as
necessary.
2. Pressure Control
Disconnect all power to the controller. Disconnect the
wires from the controller. Connect an ohmmeter between
the switch terminals. Lower the set point of the controller,
the switch should make. Raise the set point and re-check,
switch should break. if the controller operates improperly,
replace it.
4. Burner Cut-off
1. Oil tank empty
Refill the oil tank. A slight delay in the re-priming of the
fuel pump may cause the burner programmer to require
resetting before the boiler operates satisfactorily.
2. Power Supply
Check fuse or Circuit breaker. Reset or replace as
required.
3. Ignition Electrodes
Check electrodes for carbon build-up, clean if required.
Check settings adjust if required. Check for cracks in
porcelain, if found, replace.
4. UV Detector
Check for dirt on detector, clean as required. Check for
proper location of detector.
5. Faulty Air Switch
Check for faulty air switch by jumpering the two air switch
leads at the terminal block. If the boiler starts and runs with
the jumper in place, the air switch should be replaced.
6. Faulty Level Control
Check the level control relays are securely mounted on
their bases. Check the power supply to each. The relays
may be checked by swapping positions and checking they
are both functioning.
7. Oil Nozzle
Check for clogged nozzle, clean or replace.
8. Transformer
Check voltage between transformer neutral at terminal
block to be sure transformer is being powered.
9. Burner Control
Check voltage between pilot terminal and neutral and
ignition terminal and neutral. Check must be made before
the control locks out on safety. If no power replace control.
10. Pressure Control
Disconnect all power to the controller. Disconnect the
wires from the controller. Connect an ohmmeter between
the switch terminals. Lower the set point of the controller,
the switch should make raise the set point and re-check,
switch should break. If the controller operates improperly,
replace it.
6.2
TROUBLESHOOTING
OIL BOILER
Содержание VMP Series
Страница 8: ...VMP IOMM 2018 2 Fulton Ltd Page VIII...
Страница 25: ...VMP IOMM 2018 2 Fulton Ltd Page 17 INSTALLATION 2 Figure 10 Electrical Customer Terminal Connections...
Страница 30: ...VMP IOMM 2018 2 Fulton Ltd Page 22...
Страница 66: ...VMP IOMM 2018 2 Fulton Ltd Page 58...
Страница 100: ...VMP IOMM 2018 2 Fulton Ltd Page 92...
Страница 102: ...VMP IOMM 2018 2 Fulton Ltd Page 94 APPENDIX C...