Page 65
TROUBLESHOOTING - 6
6.2
TROUBLESHOOTING
OIL BOILER
CONTINUED ON NEXT PAGE
Problem
Cause
Remedy
5. Poor combustion
1. Refractory bricks
Check the bricks are not plugged with soot or broken into
pieces. Clean and replace as required.
2. Stainless steel ring
Check to ensure the ring is present and fits securely
against the furnace wall.
3. Main air adjustment
Check air adjustment. Open main air until fire brushes the
furnace wall.
4. Secondary air adjustment.
Check main air adjustment to see if it has moved. Adjust
as necessary and tighten in position. Check CO
2
and O
2
level.
5. Draft
Check draft is neutral. Consider installing a barometric
damper if the draft is too strong.
6.
Dirty flue
Check flue for Carbon build-up or blockage. Clean flue
passages with brush.
7. Negative room pressure
Ensure no exhaust fans are running in the boiler room.
8. Oil nozzle
Check for blocked nozzle, clean or replace as necessary.
9. Oil pump
Check for blocked strainer or filter. Remove or clean.
Check for slipping or broken coupling. Tighten or replace.
Check for seized pump shaft. Replace.
6.
Burner back fires
1. Refractory bricks
Check the bricks are not plugged with soot or broken into
pieces. Clean and replace as required.
2. Ignition electrodes
Check electrodes for carbon build-up, clean if required.
Check settings adjust if required. Check for cracks in
porcelain, if found, replace.
3. UV detector
Check for dirt on scanner, clean as required. Check for
proper location of detector.
4. Draft problem
Check draft is neutral. Consider installing a barometric
damper if the draft is too strong.
5. Negative room pressure
Ensure no exhaust fans are running in the boiler room.
6. Primary air adjustment
Check air adjustment. Air may be blowing fire
away from flame detector.
7. Oil valve(s)
Check for leaking oil valve(s) and replace.
8. Loss of oil prime
Check all lines for possible air leak in intake line and
tighten. Check for possible restricted intake line. Replace.
9.
Loose oil fittings
Check all fittings and tighten.
10.
Blocked oil filter
Check and clean or replace.
11. Blocked screen in oil pump
Check and clean or replace.
12.
Blocked flue
Check flue is not blocked, clean as required.
Check draft at flue.
13. Vacuum on pump
Check for too high a vacuum on the pump.
Check oil lines and distance from tank to boiler.
Repair or replace as necessary.
14. Hole in suction line
Check and replace as necessary.
Содержание VMP Series
Страница 8: ...VMP IOMM 2018 2 Fulton Ltd Page VIII...
Страница 25: ...VMP IOMM 2018 2 Fulton Ltd Page 17 INSTALLATION 2 Figure 10 Electrical Customer Terminal Connections...
Страница 30: ...VMP IOMM 2018 2 Fulton Ltd Page 22...
Страница 66: ...VMP IOMM 2018 2 Fulton Ltd Page 58...
Страница 100: ...VMP IOMM 2018 2 Fulton Ltd Page 92...
Страница 102: ...VMP IOMM 2018 2 Fulton Ltd Page 94 APPENDIX C...