background image

RM7895A RELAY MODULE

32-00122-01

16

CHECKOUT

WARNING

Fire or Explosion Hazard.
Can cause serious injury, death or property 
damage.

Do not allow fuel to accumulate in the combustion 
chamber. If fuel is allowed to enter the combustion 
chamber for longer than a few seconds without 
igniting, an explosive mixture could result.

It is recommended that you limit the trial for pilot to 
ten seconds, and limit the attempt to light the main 
burner two seconds from the time the fuel has 
reached the burner nozzle. In any case, do not 
exceed the nominal lightoff time specified by the 
equipment manufacturer. Close the manual fuel 
shutoff valves if the flame is not burning at the end 
of the specified time.

WARNING

Electrical Shock Hazard.
Can cause serious injury or death.

1. Use extreme care while testing the system. Line 

voltage is present on most terminal connections 
when power is on.

2. Open the master switch before removing or 

installing the RM7895.

3. Make sure all manual fuel shutoff valves are 

closed before starting the initial lightoff check 
and the Pilot Turndown tests.

4. Do not put system in service until you have 

satisfactorily completed all applicable tests in 
this section and any others required by the 
equipment manufacturer.

CAUTION

Equipment Damage Hazard.
Can damage equipment or cause improper 
operation.

If an RM7895 is replaced with a lower or higher 
functioning 7800 SERIES Relay Module, the 
burner will not sequence unless wiring changes are 
made.

IMPORTANT

1. If the system fails to perform properly, refer to 

7800 SERIES System Annunciation Diagnostics 
and Troubleshooting, form 65-0233.

2. Repeat ALL required Checkout tests after all 

adjustments are made. ALL tests must be satisfied 
with the flame detector(s) in the FINAL position.

Equipment Recommended

Volt-ohmmeter (1 Mohm/volt minimum sensitivity) with:

• 0-300 Vac capability.

• 0-6000 ohm capability.

• 0-10 Vdc capability.

Checkout Summary

• Preliminary inspection—all installations.

• Flame signal measurement—all installations.

• Initial lightoff check for proved pilot—all installations 

using
        a pilot.

• Initial lightoff check for direct spark ignition of oil—all

        burners using DSI.

• Pilot turndown test—all installations using a pilot.

• Hot refractory hold-in test—all installations.

• Ignition interference test—all installations using 

        flame rods.

• Ignition spark pickup—all installations using 

Ultraviolet
        Flame Detectors.

• Response to other ultraviolet sources—all 

installations
        using Ultraviolet Flame Detectors.

• Flame signal with hot combustion chamber—all

        installations.

• Safety shutdown tests—all installations.

See Fig. 1 for location of component parts and see Fig. 5 or 
Q7800 Specifications for terminal locations.

Preliminary Inspection

Perform the following inspections to avoid common 
problems. Make certain that:

1.

Wiring connections are correct and all terminal 
screws are tight.

2.

Flame detector(s) is (are) clean, installed and 
positioned properly. Consult the applicable 
Instructions.

3.

Correct combination of flame amplifier and flame 
detector(s) is used. See Table 2 in the Specifications 
section.

4.

Plug-in amplifier and purge card are securely in 
place.

5.

Burner is completely installed and ready to fire; con-
sult equipment manufacturer instructions. Fuel 
lines are purged of air.

6.

Combustion chamber and flues are clear of fuel and 
fuel vapor.

7.

Power is connected to the system disconnect switch 
(master switch).

8.

Lockout switch is reset (push in reset push button) 
only if the RM7895 is powered, see Fig. 1.

9.

System is in the STANDBY condition. POWER LED is 
energized.

10.

All limits and interlocks are reset.

Flame Signal Measurement (Fig. 17 and Table 8).

Содержание RM7895A

Страница 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Страница 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Страница 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Страница 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Страница 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Страница 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Страница 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Страница 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Страница 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Страница 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Страница 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Страница 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Страница 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Страница 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Страница 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Страница 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Страница 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Страница 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Страница 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Страница 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Страница 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Страница 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Страница 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Страница 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Отзывы: