background image

RM7895A RELAY MODULE

32-00122-01

18

3.

Close the master switch and start the system with a 
call for heat by raising the set point of the operating 
controller, see Fig. 11 or 13. The primary sequence 
should start the  ten-second INITIATE sequence.

4.

Let the sequence advance through PREPURGE. 
Ignition spark should occur and the pilot should 
light. If the pilot ignites, the FLAME LED will be 
energized. Proceed to step 7.

5.

If the pilot flame is not established in four or ten 
seconds, safety shutdown occurs. Let the sequence 
complete its schedule. Consult the equipment 
operating manual for further information.

6.

Push the reset push button and let the system recy-
cle once. If the pilot still does not ignite, make the 
following ignition/pilot adjustments.
a. Open the master switch and remove the RM7895 

from the subbase.

b. On the subbase, jumper terminal 5 to ignition 

terminal 8 or 10; refer to the appropriate wiring 
diagram to determine the proper terminal. 
Disconnect the leadwire to the pilot valve if it is 
connected to the same terminal.

c. Close the master switch to energize only the igni-

tion transformer.

d. If the ignition spark is not strong and continuous, 

open the master switch and adjust the ignition 
electrode spark gap setting to the manufacturer 
recommendations.

e. Make sure the ignition electrodes are clean.
f.

Close the master switch and observe the spark.

g. After a continuous spark is obtained, open the 

master switch and add a jumper on the subbase 
from terminal 5 (L1) to the pilot terminal 8. 
Reconnect the leadwire from the pilot valve if it 
was disconnected in step b.

h. Close the master switch to energize both the 

ignition transformer and the pilot valve.

i.

If the pilot does not ignite and if the ignition 
spark is still continuous, adjust the pressure reg-
ulator until a pilot is established.

j.

When the pilot ignites properly and stays ignited, 
open the master switch and remove the 
jumper(s) from terminals 5-8  or 5-10 of the sub-
base.

k. Check for adequate bleeding of the fuel line.
l.

Reinstall the RM7895 on the subbase and close 
the master switch, then return to step 4.

7.

When the pilot ignites, measure the flame signal. If 
pilot flame signal is unsteady or approaching the 
1.25 Vdc minimum value, adjust the pilot flame size 
or detector sighting to provide a maximum and 
steady flame signal.

8.

Recycle the system to recheck lightoff and pilot 
flame signal.

9.

When the MAIN IGN period is displayed by the MAIN 
LED, make sure the automatic main fuel valve is 
open; then smoothly open the manual main fuel 
shutoff valve(s) and watch for main burner flame 
ignition. When the main burner flame is established, 
proceed to step 16.

10.

If the main burner flame is not established within 
five seconds, or the normal lightoff time specified by 
the equipment manufacturer, close the manual main 
fuel shutoff valve(s).

11.

Recycle the system to recheck the lightoff and pilot 
flame signal.

12.

Smoothly open the manual fuel shutoff valve(s) and 
try lightoff again. (The first reattempt may have been 
required to purge the lines and bring sufficient fuel 
to the burner.)

13.

If the main burner flame is not established within 
five seconds or the normal lightoff time specified by 
the equipment manufacturer, close the manual main 
fuel shutoff valve(s). Check all burner adjustments.

14.

If the main burner flame is not established after two 
attempts:
a. Check for improper pilot size.
b. Check for excess combustion air.
c. Check for adequate fuel flow.
d. Check for proper gas supply pressure.
e. Check for proper valve operation.
f.

Check for proper pilot flame positioning.

15.

Repeat steps 8 through 14 to establish the main 
burner flame; then proceed to step 16.

16.

With the sequence in RUN, make burner adjust-
ments for flame stability and BTU input ratings.

17.

Shut down the system by opening the burner switch 
or by lowering the set point of the operating control-
ler. Make sure the main flame goes out. There may 
be a delay due to gas trapped between the valve(s) 
and the burner. Make sure all automatic fuel valves 
close.

18.

Restart the system by closing the burner switch 
and/or raising the set point of the operating control-
ler. Observe that the pilot is established during 
PILOT IGN and the main burner flame is established 
during MAIN IGN within the normal lightoff time.

19.

Measure the flame signal. Continue to check for the 
proper signal, see Table 7, through the RUN period.

20.

Run the burner through another sequence, observ-
ing the flame signal for:
a. Pilot flame alone (unless using direct spark igni-

tion).

b. Pilot and main flame together.
c. Main flame alone (unless monitoring an inter-

mittent pilot).

21.

Also observe the time it takes to light the main flame. 
Ignition of the main flame should be smooth.

22.

Return the system to normal operation.

23.

Make sure all readings are in the required ranges 
before proceeding.

NOTE:

Upon completing these tests, open the master 
switch and remove all test jumpers from the 
subbase terminals, limits/controls or switches.

Initial Lightoff Check for Direct 
Spark Ignition

This check applies for gas and oil burners that do not use a 
pilot. It should immediately follow the preliminary 
inspection. Refer to the appropriate sample block diagram 
of field wiring for the ignition transformer and fuel valve(s) 
hookup.

NOTE:

Low fuel pressure limits, if used, could be open. If 
so, bypass them with jumpers during this check.

1.

Open the master switch.

2.

Complete the normal checkout of the fuel supply 
and equipment as recommended by the equipment 
manufacturer.

Содержание RM7895A

Страница 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Страница 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Страница 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Страница 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Страница 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Страница 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Страница 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Страница 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Страница 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Страница 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Страница 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Страница 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Страница 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Страница 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Страница 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Страница 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Страница 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Страница 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Страница 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Страница 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Страница 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Страница 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Страница 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Страница 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Отзывы: