background image

RM7895A RELAY MODULE

17

32-00122-01

Table 8. Flame Signal.

a

 This minimum or a stronger signal should easily be obtained if the detector is correctly installed and positioned to prop-

erly sense the flame. This voltage must be obtained before completing checkout.

Fig. 14. Flame signal measurement.

Measure the flame signal at the appropriate times defined 
in the following checkout tests. Read the flame signal volts 
dc at the flame amplifier test jacks + and - (Com).

1.

Use a 1 Megohm/volt meter with a 0 to 10 Vdc 
capability.

2.

Set the meter to the 0 to 10 Vdc range.

3.

Insert the positive (red) probe into the + jack of the 
flame amplifier. Insert the negative (black) probe 
into the - (Com) jack of the flame amplifier. See Fig. 
14.

4.

Allow a few seconds for the meter reading to stabi-
lize.

5.

The meter reading must be as specified in Table 8 
after all tests are completed and all adjustments are 
made.

As an option, the flame signal can be checked by using the 
optional Keyboard Display Module.

If the signal is unstable or less than the minimum 
acceptable voltage, check the flame detector installation 
and circuitry.

1.

Check the supply voltages at terminals 5 (L1) and 
L2(N). Make sure the master switch is closed, 
connections are correct, and the power supply is of 
the correct voltage and frequency and is sinusoidal.

2.

Check the detector wiring for defects including: 

Incorrect connections.

• Wrong type of wire.

• Deteriorated wire.

• Open circuits.

• Short circuits.

• Leakage paths caused by moisture, soot or 

accumulated
        dirt.

3.

For flame rod, make sure:

• Ground area is large enough.

• Flame rod is properly located in the flame.

• Temperature at the flame rod insulator is no greater 

than
        500°F (260°C).

4.

For all optical detectors, clean the detector viewing 
window and inside of the sight pipe as applicable.

5.

With the burner running, check the temperature at 
the detector. If it exceeds the detector maximum 
rated temperature:

• Add a heat block to stop conducted heat traveling up 

        the sight pipe.

• Add a shield or screen to reflect radiated heat.

• Add cooling (refer to sight pipe ventilation in the 

detector 
        instructions).

6.

Make sure that the flame adjustment is not too lean.

7.

Make sure that the detector is properly sighting the 
flame.

8.

If necessary, resight or reposition the detector.

Initial Lightoff Check for Proved 
Pilot

Perform this check on all installations that use a pilot. It 
should immediately follow the preliminary inspection.

NOTE:

Low fuel pressure limits, if used, could be open. If 
so, bypass them with jumpers during this check.

1.

Open the master switch.

2.

Make sure that the manual main fuel shutoff valves 
are closed. Open the manual pilot shutoff valve. If 
the pilot takeoff is downstream from the manual 
main fuel shutoff valve(s), very slightly open the 
manual main valve to supply pilot gas flow. Make 
sure the main fuel is shutoff just upstream from the 
burner inlet, or disconnect power from the automatic 
main fuel valves.

Flame Detector

Acceptable Flame Signal 

Amplifier

Minimum Maximum 

Steady dc Voltage

a

Expected dc Voltage

Flame Rod
C7012A,C

R7847A

1.25 Vdc

5.0 Vdc at the Keyboard 
Display Module

or

5.0 Vdc at a 1 Megohm/volt 
meter.

C7027A
C7035A
C7044A

R7849A

1 MEGOHM/VOLT

METER

M20281

POSIIVE (+)

METER LEAD

NEGATIVE (–)

METER LEAD

Содержание RM7895A

Страница 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Страница 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Страница 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Страница 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Страница 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Страница 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Страница 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Страница 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Страница 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Страница 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Страница 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Страница 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Страница 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Страница 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Страница 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Страница 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Страница 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Страница 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Страница 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Страница 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Страница 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Страница 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Страница 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Страница 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Отзывы: