background image

RM7895A RELAY MODULE

19

32-00122-01

3.

Close all manual main fuel shutoff valves. Check 
that the automatic fuel valves are closed. Make sure 
fuel is not entering the combustion chamber. 

4.

Close the master switch and start the system with a 
call for heat by raising the set point of the operating 
controller, see Fig. 11. The primary sequence should 
start the ten-second INITIATE sequence.

5.

Let the sequence advance through PREPURGE. 
Ignition spark should occur after the PREPURGE 
period. Listen for the click of the first stage fuel 
solenoid valve(s).

6.

Let the program sequence complete its cycle.

7.

Open the manual fuel shutoff valve(s).

8.

Reset the Lockout Switch and recycle the primary 
sequence through PREPURGE.

9.

Watch for the FLAME LED to help determine when 
the first stage burner flame is established. If it is 
established, proceed to step 15.

10.

If the first stage burner flame is not established 
within four seconds, or within the normal lightoff 
time specified by the equipment manufacturer, close 
the manual fuel shutoff valve(s) and open the 
master switch.

11.

Check all burner adjustments.

12.

Wait about three minutes. Close the master switch, 
open the manual fuel shutoff valve(s), and try again 
to lightoff the burner. The first attempt may have 
been required to purge the lines and bring sufficient 
fuel to the burner.

13.

If the first stage burner flame is not established 
within four seconds, or within the normal lightoff 
time specified by the equipment manufacturer, close 
the manual fuel shutoff valve(s) and open the 
master switch.

14.

If necessary, repeat steps 8 through 13 to establish 
the first stage burner flame. Then proceed to step 
15.

15.

When the first stage burner flame is established, the 
sequence will advance to RUN. Make burner 
adjustments for flame stability and input rating. If a 
second stage is used, proceed to step 18.

16.

Shut down the system by opening the burner switch 
or by lowering the set point of the operating 
controller. Make sure the burner flame goes out and 
make sure all automatic fuel valves close.

17.

If used, remove the bypass jumpers from the low fuel 
pressure limit and subbase.

18.

If a second stage is used, make sure the automatic 
second stage fuel valve(s) has opened and check the 
lightoff as follows. Otherwise, proceed to step 19.
a. Open the manual second stage fuel valve(s).
b. Restart the system by raising the set point of the 

operating controller.

c. When the first stage burner flame is established, 

watch for the automatic second stage fuel 
valve(s) to open. Observe that the second stage 
lights off properly.

d. Make burner adjustments for flame stability and 

input rating.

e. Shut down the system by lowering the set point 

of the operating controller. Make sure the burner 
flame goes out and all automatic fuel valves 
close. Proceed to step 19.

19.

Restart the system by closing the burner switch 
and/or raising the set point of the operating control-
ler. Observe that the burner flame is established 
during PILOT IGN, within the normal lightoff time 
specified by the equipment manufacturer.

20.

Measure the flame signal. Continue to check for the 
proper signal, see Table 8, through the RUN period. 
Any pulsating or unsteady readings will require 
further attention.

21.

Make sure all readings are in the required ranges 
before proceeding.

NOTE:

Upon completing these tests, open the master 
switch and remove all test jumpers from the sub-
base terminals, limits/control or switches.

22.

Return the system to normal operation.

Pilot Turndown Test (All 
Installations Using a Pilot)

Perform this check on all installations that use a pilot. The 
purpose of this test is to verify that the main burner can be 
lit by the smallest pilot flame that will hold in the flame 
amplifier and energize the FLAME LED. Clean the flame 
detector(s) to make sure it will detect the smallest 
acceptable pilot flame.

NOTE:

Low fuel pressure limits, if used, could be open. If 
so, bypass them with jumpers during this test.

1.

Open the master switch.

2.

Close the manual main fuel shutoff valve(s).

3.

Connect a manometer (or pressure gauge) to mea-
sure the pilot gas pressure during the turndown test.

4.

Open the manual pilot shutoff valve(s).

5.

Close the master switch and start the system with a 
call for heat. Raise the set point of the operating 
controller. The primary sequence should start and 
PREPURGE should begin.

NOTE:

INTERMITTENT PILOT MODELS should continue 
with step 6.

6.

INTERMITTENT PILOT MODELS—After the 
sequence has entered the normal burner run period, 
turn the pilot gas pressure down very slowly, reading 
the manometer (or gauge) as the pressure drops. 
Stop immediately when the FLAME LED goes out. 
Note the pressure at this point.
a. If the Flame Failure Action jumper is not clipped: 

allow the RM7895A to recycle through PRE-
PURGE. If the Flame Failure Action jumper is 
clipped: push the reset push button and allow 
the RM7895A to recycle through PREPURGE.

b. As the control attempts to relight the pilot, turn 

the pilot gas pressure back up slowly until the 
FLAME LED comes on. This step must be com-
pleted within 4 or 10 seconds, depending on the 
selected PFEP, or lockout will occur.

c. Turn the pilot back down slightly but not enough 

to cause the FLAME LED to go out. (Keep the gas 
pressure just above the reading noted in step 6 
above.)

NOTE:

Step d requires two people, one to open the man-
ual main fuel valve(s) and one to watch for igni-
tion.

Содержание RM7895A

Страница 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Страница 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Страница 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Страница 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Страница 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Страница 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Страница 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Страница 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Страница 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Страница 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Страница 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Страница 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Страница 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Страница 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Страница 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Страница 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Страница 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Страница 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Страница 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Страница 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Страница 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Страница 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Страница 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Страница 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Отзывы: