background image

RM7895A RELAY MODULE

11

32-00122-01

a. Allow an additional two inches below the 

RM7895 for the flame amplifier mounting.

b. Allow an optional three-inch minimum to both 

sides of the RM7895 for electrical signal voltage 
probes. 

3.

Make sure no subbase wiring is projecting beyond 
the terminal blocks. Tuck wiring in against the back 
of the subbase so it does not interfere with the knife 
blade terminals or bifurcated contacts.

4.

Mount the RM7895 by aligning the four L-shaped 
corner guides and knife blade terminals with the 
bifurcated contacts on the wiring subbase and tight-
ening the two screws securely without deforming the 
plastic.

IMPORTANT:

Install the RM7895 with a plug-in motion rather 
than a hinge action.

Installing ST7800 Purge Card

1.

Remove the Dust Cover, Keyboard Display Module, 
Data ControlBus™ Module, or Extension Cable 
Assembly.

2.

Remove the current ST7800 from the RM7895 by 
pulling upward on the plastic support cover, see Fig. 
7.

3.

Make sure the ST7800A selected has the desired 
timing.

4.

Insert the Purge Card into the opening of the 
RM7895. (Again, see Fig. 7.)

5.

Reinstall the Dust Cover, Keyboard Display Module, 
Data ControlBus™ Module, or Extension Cable 
Assembly onto the RM7895 and restore power to the 
device.

6.

Run the burner system through at least one com-
plete cycle to verify that the system is operating as 
desired.

Mounting Dust Cover

1.

Align the two interlocking ears of the Dust Cover with 
the two mating slots on the RM7895, see Fig. 8.

2.

Insert the two interlocking ears into the two mating 
slots, and, with a hinge action, push on the upper 
corners of the Dust Cover to secure it to the 
RM7895.

3.

Be sure the Dust Cover is firmly in place.

Installing Plug-in Flame Signal 
Amplifier

1.

Disconnect the power supply before beginning 
installation to prevent electrical shock and 
equipment damage. More than one disconnect may 
be involved.

2.

Align the amplifier circuit board edge connector with 
the keyed receptacle on the RM7895. Ensure the 
amplifier nameplate faces away from the relay mod-
ule. See Fig. 9.

3.

Push in the amplifier until the circuit board is fully 
inserted into the receptacle and then push the 
amplifier toward the RM7895 retaining clasp.

4.

Verify the amplifier is firmly in place.

5.

Restore power.

Perform all required checkout tests.

Installing the Flame Detector

NOTE:

Table 2 and Fig. 10 list the flame detection 
systems available for use with theRM7895. Make 
sure the correct combination of amplifier and 
flame detector(s) is used.

Proper flame detection installation is the basis of a safe 
and reliable flame safeguard installation. Refer to the 
instructions packed with the flame detector and the 
equipment manufacturer instructions.

Keep the flame signal leadwires as short as possible from 
the flame detector to the wiring subbase. Capacitance 
increases with leadwire length, reducing the signal 
strength. The maximum permissible leadwire length 
depends on the type of flame detector, leadwire and 
conduit. The ultimate limiting factor in the flame detector 
leadwire is the flame signal, see Table 8. 

Fig. 6. Electrical panel installation.

Fig. 7. ST7800 Purge Card installation.

Содержание RM7895A

Страница 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Страница 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Страница 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Страница 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Страница 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Страница 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Страница 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Страница 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Страница 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Страница 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Страница 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Страница 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Страница 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Страница 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Страница 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Страница 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Страница 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Страница 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Страница 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Страница 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Страница 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Страница 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Страница 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Страница 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Отзывы: