background image

RM7895A RELAY MODULE

32-00122-01

6

Closed Loop Logic Test

The test verifies the integrity of all safety critical loads, 
terminals 8, 9, 10 and 21. If the loads are not energized 
properly; i.e., the main valve terminal is powered during 
PREPURGE, the RM7895 will lock out on safety shutdown. 
The RM7895 must react to input changes but avoid the 
occurrence of nuisance shutdown events. Signal 
conditioning is applied to line voltage inputs to verify 
proper operation in the presence of normal electrical line 
noise such as transient high voltage spikes or short 
periods of line drop out. Signal conditioning is tolerant of 
synchronous noise (line noise events that occur at the 
same time during each line cycle).

Dynamic Input Check

All system input circuits are examined to assure that the 
RM7895 is capable of recognizing the true status of 
external controls, limits and interlocks. If any input fails 
this test, a safety shutdown occurs and the fault will be 
annunciated.

Dynamic Safety Relay Test

Checks the ability of the dynamic safety relay contact to 
open and close. Verifies that the safety critical loads, 
terminals 8, 9, 10 and 21, can be de-energized, as 
required, by the Dynamic Self-Check logic.

Dynamic Self-Check Safety Circuit

The microcomputer  tests itself and related hardware, and 
at the same time, the safety relay system tests the 
microcomputer operation. If a microcomputer or safety 
relay failure occurs and does not allow proper execution of 
the 
self-check routine, safety shutdown occurs and all safety 
critical loads will be de-energized.

Expanded Safe-Start Check

The conventional safe-start check, which prevents burner 
startup of flame is indicated at startup, is expanded to 
include a flame signal check during STANDBY, an airflow 
switch check and a safety critical load check.

Off Cycle (Standby or Prepurge) 
Flame Signal Check

The flame detection subsystem (flame detector and 
amplifier) is monitored during STANDBY. If a flame 
simulating condition or an actual flame exists, a system 
hold occurs and startup is prevented. If the flame signal 
exists at any time after the first 40 seconds of STANDBY, a 
safety shutdown occurs and is annunciated. A shutter-
check amplifier and self-checking detector are energized 
for the first 40 seconds during STANDBY and the last two 
seconds before exiting STANDBY. If a flame exists, a safety 

shutdown occurs. A standard amplifier is energized 
continually through STANDBY and PREPURGE; if a flame 
exists, a safety shutdown occurs.

Tamper Resistant Timing and Logic

Safety and logic timings are inaccessible and cannot be 
altered or defeated.

Verified Spark Termination

The ignition terminal is monitored to assure early spark 
termination (ten seconds ignition and pilot and ten 
seconds 

pilot and main only

).

First-Out Annunciation and Self-
Diagnostics

Sequence Status Lights (LEDs)

 provide positive visual 

indication of the program sequence: POWER, PILOT, 
FLAME, MAIN and ALARM. The green POWER LED blinks 
every four seconds, signifying that the RM7895 hardware 
is running correctly.

Optional multi-function Keyboard Display Module

 shows 

elapsed time during PREPURGE, PILOT IGN and MAIN 
IGN. As an additional troubleshooting aid, it provides 
sequence timing, diagnostic information, historical 
information and expanded annunciator information when 
a safety shutdown or hold or normal operation occurs.

First-Out Annunciation

 reports the cause of a safety 

shutdown or identifies the cause of a failure to start or 
continue the burner control sequence with an English text 
and numbered code via the optional Keyboard Display 
Module. It monitors all field input circuits, including the 
flame signal amplifier. The system distinguishes 43 
modes of failure and detects and annunciates difficult-to-
find intermittent failures.

Self-Diagnostics

 add to the First-Out Annunciation by 

allowing the RM7895 to distinguish between field 
(external device) and internal (system related) problems. 
Faults associated within the flame detection subsystem, 
RM7895 or Plug-in Purge Card are isolated and reported 
by the optional Keyboard Display Module. See the 7800 
SERIES System Annunciation Diagnostics and 
Troubleshooting, Form 65-0233.

Interlock Requirements

The following interlock input is provided:

Airflow Switch Interlock

This interlock is typically connected to an airflow switch. 
The Airflow Interlock (ILK) input must close ten seconds 
into PREPURGE or within the specified purge card timing; 
otherwise, a recycle to the beginning of PREPURGE or 
lockout will occur, depending on how the airflow switch 
selectable jumper is configured (see Table 6).

Содержание RM7895A

Страница 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Страница 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Страница 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Страница 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Страница 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Страница 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Страница 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Страница 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Страница 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Страница 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Страница 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Страница 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Страница 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Страница 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Страница 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Страница 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Страница 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Страница 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Страница 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Страница 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Страница 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Страница 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Страница 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Страница 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Отзывы: