Trouble shooting 6
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
17.8
26.3
20
40.0
62.5
-30
1013.1
-20
531.6
-10
292.9
-5
221.1
79.1
100.9
129.8
168.6
Resistance value (k )
15
10
5
0
Temperature (
°C )
12.3
30
50
40
60
2.0
3.4
4.6
6.3
8.7
Resistance value (k )
120
100
90
80
70
Temperature (
°C )
Outdoor Discharge Pipe Temperature
Thermistor Error
Outdoor unit Main PCB
Discharge pipe temperature thermistor
When Discharge pipe temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-08
Refer to error code table.
CN71
CN70
THERMISTOR
( DISCHARGE PIPE )
THERMISTOR
( HEAT EXCHANGER )
THERMISTOR
( OUTDOOR TEMP. )
1
4
2
3
1
4
2
3
1
2
3
1
2
3
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK