3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor speed is decreased on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than 4
°C
.
Then, the anti-freezing control is released when it becomes higher than Release temperature A.
(Table 22 : Anti-freezing protection operation / Release temperature)
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to
67°C
or greater,
the compressor is stopped.
Then the compressor will be restarted after 3 minutes ST.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
In heating mode, the compressor speed is controlled based on the detection value
of the indoor heat exchanger temperature sensor.
01-20
Outdoor temperature zone
A, B , C, D
7°C
13°C
Release temperature A
E, F
Indoor heat exchange
temperature rises
Indoor heat exchange
temperature drops
[ Control System ]
It returns to the normal operation
53°C
50°C
The compressor speed is
decreased 3rps every 60seconds.
5-1. HIGH TEMPERATURE RELEASE CONTROL of Outdoor Unit
Indoor heat exchange
temperature rises
Indoor heat exchange
temperature drops
[ Control System ]
It returns to the normal operation
55°C
52°C
5-2. HIGH TEMPERATURE RELEASE CONTROL of Indoor Unit
Refer to below
Compressor operation
57rps or more 55rps
35 ~ 55rps Rotational speed down every 120 sec
28 ~ 33rps 23rps
18 ~ 23rps OFF
[ ASYA09LEC ]
Compressor operation
48rps or more 45rps
39 ~ 45rps Rotational speed down every 120 sec
27 ~ 36rps 25rps
18 ~ 25rps OFF
[ ASYA12LEC ]