3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 3.
However, after the compressor is driven, the indoor unit shall run at operation frequency of
52rps (for ASYA09LEC) or 61rps (for ASYA12LEC) , for a minute.
Ts+
0.5°C
Ts -1.5
°C
Ts -0.5
°C
Ts+1.5
°C
( Table 3 : Compressor frequency )
( Fig.3 : Compressor control based on room temperature )
01-03
Operating
speed
30rps
23rps
0rps
09LEC
X zone
J zone
Y zone
Operating
speed
J zone
Y zone
X zone
33rps
25rps
0rps
12LEC
Room Room
temperature drops temperature rises
X zone
J zone
Y zone