Trouble shooting 25
Forecast of Cause:
Check Point 2 : Check outdoor unit operation
Check Point 1 : Check indoor unit
Check Point 3 : Check site condition
Check Point 5 : Check refrigeration cycle
Check Point 4 :
Check indoor unit / outdoor unit installation condition
Pipe (In)
Pipe (Out)
Pipe (In)
Pipe (Out)
OK
OK
OK
OK
OK
OK
OK
OK
No Cooling / No Heating
1. Indoor unit error 2. Outdoor unit error
3. Effect by surrounding environment
4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure
6. Heater Unit failure
Does indoor unit Fan run on high fan?
Is Air Filter dirty?
Is Heat Exchanger clogged?
Check if energy save function is operated.
Is outdoor unit is operating?
(If not, refer to Trouble shooting 23)
Is there any obstructing the air flow route?
Is there any clogging on outdoor unit Hert Exchanger?
Is the valve open?
Is capacity of indoor unit fitted to room size?
Any windows open? Or direct sunlight?
Check connection pipe.
(Specified pipe length and pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data & Technical
Manual.
Check if Strainer is clogged (Refer to the figure at right).
Measure gas pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3)
Check Compressor (PARTS INFORMATION 1,2)
Check Heater Unit (PARTS INFORMATION 6)
Strainer normally does not have temperature difference
between inlet and outlet as shown in , but if there is a
difference like shown in , there is a possibility of inside
clogged. In this case, replace Strainer.
02-27
MPa MPa