Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
The maximum value of the indoor fan speed is set as shown in Figure 7, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.7 : Cool air prevention control)
01-06
6. COOL AIR PREVENTION CONTROL (Heating mode)
7. ECONOMY FAN CONTROL (Dry mode)
47°C
40°C
37°C
Cool air prevention
30°C
S-Lo
40°C
28°C
32°C
35°C
<Before 7 minutes upon running the compressor>
Lower of "Hi" and "setting fan speed"
Lower of "Me+" and "setting fan speed"
Lower of "Lo" and "setting fan speed"
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
47°C
40°C
40°C
35°C
<After 7 minutes upon running the compressor>
Lower of "Hi" and "setting fan speed"
Lower of "Me+" and "setting fan speed"
Lower of "Lo" and "setting fan speed"
Switch the airflow [AUTO] at dry mode, and the indoor fan motor will run as shown in Figure8.
(Table 6 : Indoor fan speed )
( Fig.8 : Indoor fan control )
Compressor
ON
OFF
Indoor fan
(as shown in Table 6)
S-Lo
OFF
10
30
60
180
60
180
60
10
30
(SEC)
X zone
J zone
ASYA09LEC
680rpm
650rpm
ASYA12LEC
680rpm
650rpm