2-4. External output
Connector
Output signal
Status
CN136 (Black)
0 V
Normal
DC 12 to 24 V
Error
CN137 (Blue)
0 V
Stop
DC 12 to 24 V
Operation
¢
Error status
This output indicates Normal or Error status of the outdoor unit and connected indoor units.
As for the required wiring specifications, refer to
1
2
+
+
-
-
CN136
(Black)
Connected unit
DC power supply
(External) 12 to 24 V
Connected load
(Operation indicator
or Error indicator)
*
3
*
1
*
2
PCB
CN136
Output
Error
12-24 V
0 V
Normal
*
1
:
Provide a DC 12 to 24 V power supply. Select a power supply capacity with an ample sur-
plus for the connected load. Do not impress a voltage exceeding 24 V across pins 1 to 2.
*
2
:
The allowable current is 30 mA or less. Provide a load resistance such that the current be-
comes 30 mA or less.
*
3
:
Polarity is “+” for pin no. 1 and “-” for pin no. 2. Connect correctly.
¢
Operation status
This output indicates Operation status of the outdoor unit.
As for the required wiring specifications, refer to
Operation
12-24 V
0 V
Stop
1
2
+
+
-
-
CN137
(Blue)
Connected unit
DC power supply
(External) 12 to 24 V
Connected load
(Operation indicator
or Error indicator)
*
3
*
1
*
2
PCB
CN137
Output
*
1
:
Provide a DC 12 to 24 V power supply. Select a power supply capacity with an ample sur-
plus for the connected load. Do not impress a voltage exceeding 24 V across pins 1 to 2.
*
2
:
The allowable current is 30 mA or less. Provide a load resistance such that the current be-
comes 30 mA or less.
*
3
:
Polarity is “+” for pin no. 1 and “-” for pin no. 2. Connect correctly.
2-4. External output
- (08-5) -
2. Outdoor unit
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT
Содержание AIRSTAGE J-IIIL
Страница 1: ...DESIGN TECHNICAL MANUAL ...
Страница 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Страница 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Страница 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Страница 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Страница 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Страница 113: ...6 2 Model AOU120RLAVL 6 2 Model AOU120RLAVL 03 17 6 Wiring diagrams OUTDOOR UNITS OUTDOOR UNITS ...
Страница 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Страница 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Страница 194: ...5 4 Mini duct type Model ARUL4TLAV1 5 4 Mini duct type 04 70 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 203: ... Models ASUA12TLAV1 and ASUA14TLAV1 5 11 Wall mounted type 04 79 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 205: ... Models ASUA30TLAV2 and ASUA36TLAV2 5 11 Wall mounted type 04 81 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 206: ... Models ASUA7TLAV and ASUA12TLAV 5 11 Wall mounted type 04 82 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Страница 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Страница 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Страница 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Страница 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Страница 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Страница 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...