Address setting by wired remote controller (UTY-RNKU)
• Indoor unit addresses and refrigerant circuit addresses can be set up using wired remote con-
trollers.
• This function allows setting the addresses of all indoor units to which a wired remote controller is
being connected.
• This function cannot be used to set up remote controller addresses.
Be sure to set them up using the rotary switches on the PCB of each indoor unit. (Refer to
• This function cannot be used on the slave units.
• This device is connectable to 3-wire type remote controller compatible models only. As for the
compatible models, refer to
"System configuration examples"
Preparation
1.
Make sure that all indoor unit address switches (IU AD x10, IU AD x1) and refrigerant circuit
address switches (REF AD x10, REF AD x1) on the PCB of each indoor unit are set at 0 (facto-
ry setting).
The layout of the switches differs by the type of the indoor unit. For the details, refer to
Rotary switch
(type A)
SW601
SW602
SW604 SW605
SW606 SW607 SW608
Check the switch position is set at “0”.
(Factory setting)
IU AD x10
IU AD x1
REF AD x10
REF AD x1
2.
If multiple indoor units are connected to a single wired remote controller, set up the remote con-
troller address (RC AD) manually on the indoor units PCBs by referring
0
1
2
3
Indoor unit
Indoor unit
Indoor unit
Indoor unit
RC AD
RC AD
RC AD
RC AD
Wired remote controller
Example: When 4 indoor units are connected
3.
Before turning on the power of indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
4.
Turn on the power of indoor units.
By turning on the power, the indoor units initialize EEV.
Indoor units
Indoor units
Breaker ON
1-4. Address setting by remote controller
- (07-26) -
1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Содержание AIRSTAGE J-IIIL
Страница 1: ...DESIGN TECHNICAL MANUAL ...
Страница 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Страница 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Страница 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Страница 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Страница 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Страница 113: ...6 2 Model AOU120RLAVL 6 2 Model AOU120RLAVL 03 17 6 Wiring diagrams OUTDOOR UNITS OUTDOOR UNITS ...
Страница 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Страница 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Страница 194: ...5 4 Mini duct type Model ARUL4TLAV1 5 4 Mini duct type 04 70 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 203: ... Models ASUA12TLAV1 and ASUA14TLAV1 5 11 Wall mounted type 04 79 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 205: ... Models ASUA30TLAV2 and ASUA36TLAV2 5 11 Wall mounted type 04 81 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 206: ... Models ASUA7TLAV and ASUA12TLAV 5 11 Wall mounted type 04 82 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Страница 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Страница 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Страница 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Страница 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Страница 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Страница 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...