Simple procedure for register data to Modbus convertor for VRF
Important
Modbus convertor for VRF will not operate, if VRF network system address (outdoor and indoor
units address) allocation information are not registered to Modbus convertor for VRF.
Address initial settings are 3 methods as follows:
Default addresses of indoor unit and outdoor unit are used (Initial
setting is not necessary)
Default address value ([Ref No.—Node No.])
Indoor unit:
[00—00] [00—01] ••• [00—63]
[01—00] [01—01] ••• [01—63]
Outdoor unit:
[00—00] [00—01] ••• [00—03]
[01—00] [01—01] ••• [01—03]
Scan of connected indoor units address
Scan procedure is as follows:
1.
Turn on the switch of scan setting.
2.
“Scan display” by LED (Address is registering inside the convertor).
3.
“Number of connected indoor unit display” by LED (Scan is complete).
4.
Turn off the switch of scan setting.
5.
“Address update display” by LED
6.
Turn on the main power again.
7.
“Address rewriting display” by LED (Address are synchronized among boards).
If scan error is generated, perform the scan again.
Setting from PC
NOTE:
For detailed information, refer to the application manual included inside packaged DVD.
1.
Install tool for convertor (software) in PC.
Tool for convertor is the accessory item of this product.
2.
Connect the PC and this product.
Connection will be done by the connector cable provided as an accessory item of this product.
3.
Set this product to USB mode.
4.
Initial setting of indoor unit and outdoor unit addresses by using the tool for convertor.
5.
Register the initial setting data to this product. Click “Register” dialog.
In this stage, this product is ready for binding and commissioning.
3-4. Modbus convertor for VRF (UTY-VMGX)
- (05-135) -
3. Adaptor/Convertor units
CONTROL
SYSTEM
CONTROL
SYSTEM
Содержание AIRSTAGE J-IIIL
Страница 1: ...DESIGN TECHNICAL MANUAL ...
Страница 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Страница 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Страница 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Страница 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Страница 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Страница 113: ...6 2 Model AOU120RLAVL 6 2 Model AOU120RLAVL 03 17 6 Wiring diagrams OUTDOOR UNITS OUTDOOR UNITS ...
Страница 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Страница 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Страница 194: ...5 4 Mini duct type Model ARUL4TLAV1 5 4 Mini duct type 04 70 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 203: ... Models ASUA12TLAV1 and ASUA14TLAV1 5 11 Wall mounted type 04 79 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 205: ... Models ASUA30TLAV2 and ASUA36TLAV2 5 11 Wall mounted type 04 81 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 206: ... Models ASUA7TLAV and ASUA12TLAV 5 11 Wall mounted type 04 82 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Страница 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Страница 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Страница 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Страница 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Страница 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Страница 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...