8-5. Compressor temperature protection
When the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. When the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition
108°C
Release condition
80°C
(3 minutes after compressor stop)
8-6. High pressure protection
Trigger condition
Pressure switch: Off (Open: Higher than 4.2 MPa)
Compressor stop
Release condition
Pressure switch: On (Close: Lower than 3.2 MPa)
(3 minutes after compressor stop)
Compressor restart
8-7. Low outdoor temperature protection
When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode
Cooling/Dry
Trigger condition
-20°C
Release condition
-15°C
8-5. Compressor temperature protection
- (04-81) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABHG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Страница 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Страница 62: ......
Страница 212: ...9 17 Model AOHG36KBTA5 02 150 9 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Страница 216: ......
Страница 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Страница 320: ......
Страница 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...