1-5. Rotation number of compressor limitation by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
•
Cooling/Dry mode
E zone
38°C
D zone
°C
C zone
B zone
A zone
12
18
°C
7°C
Unit: rps
Model name
Outdoor temperature zone
Limitation of compressor
rotation number
AOHG30KBTA4
AOHG36KBTA5
A zone
20
B zone
18
C zone
13
D zone
10
E zone
20
•
Heating mode
D zone
5°C
C zone
B zone
A zone
-1°C
-6°C
Unit: rps
Model name
Outdoor temperature zone
Limitation of compressor
rotation number
AOHG30KBTA4
AOHG36KBTA5
A zone
30
B zone
25
C zone
15
D zone
10
1-5. Rotation number of compressor limitation by outdoor temperature
- (04-17) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABHG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Страница 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Страница 62: ......
Страница 212: ...9 17 Model AOHG36KBTA5 02 150 9 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Страница 216: ......
Страница 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Страница 320: ......
Страница 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...