Heat exchanger (Middle) temperature thermistor
Temperature (°C)
Resistance (kΩ)
Voltage (V)
-30.0
95.57
0.24
-25.0
68.89
0.32
-20.0
50.31
0.43
-15.0
37.19
0.57
-10.0
27.81
0.73
-5.0
21.02
0.92
0.0
16.05
1.14
5.0
12.38
1.39
10.0
9.63
1.65
15.0
7.56
1.93
20.0
5.98
2.21
25.0
4.77
2.49
30.0
3.84
2.77
35.0
3.11
3.02
40.0
2.53
3.26
45.0
2.08
3.48
50.0
1.71
3.67
55.0
1.42
3.85
60.0
1.19
4.00
65.0
1.00
4.13
70.0
0.84
4.25
75.0
0.71
4.35
80.0
0.61
4.43
¢
Outdoor temperature thermistor
Temperature (°C)
Resistance (kΩ)
Voltage (V)
-30.0
224.3
0.73
-25.0
159.7
0.97
-20.0
115.2
1.25
-15.0
84.2
1.56
-10.0
62.3
1.90
-5.0
46.6
2.26
0.0
35.2
2.61
5.0
26.9
2.94
10.0
20.7
3.25
15.0
16.1
3.52
20.0
12.6
3.76
25.0
10.0
3.97
30.0
8.0
4.14
35.0
6.4
4.28
40.0
5.2
4.41
45.0
4.2
4.51
50.0
3.5
4.59
55.0
2.8
4.65
6-2. Outdoor unit
- (03-98) -
6. Thermistor resistance values
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABHG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Страница 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Страница 62: ......
Страница 212: ...9 17 Model AOHG36KBTA5 02 150 9 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Страница 216: ......
Страница 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Страница 320: ......
Страница 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...