Setting up each indoor unit
Repeat step from 1. to 8. to set up each indoor unit. If the custom code is other than " ", steps from
1. to 2. and 8. need to be performed.
Resetting the power after setting up all indoor units
Important:
• If the reset is not performed, function cannot be read correctly.
• After all the functions have been set, the circuit breaker needs to be switched off for at least 2
minutes.
– After the 2 minutes has passed, power can be restored.
– The set function is stored in the PCB and will remain in memory even when the power of in-
door unit is turned off.
However setting function is effective after disconnecting the power supply and then recon-
necting it.
• Record the latest configuration of the indoor unit function setting on a label, and put the label on
the unit so it can be used for after-sales service operations.
Once the RESET button is pressed on the remote controller, the operation mode will be set to the
AUTO MODE.
Adjust the operation mode to either cooling or heating before starting the operation of the air condi-
tioner.
NOTE:
If custom code other than " " is set, the remote control must be set accordingly to the in-
door unit setting.
1-2. Indoor unit (setting by wireless remote controller)
- (05-18) -
1. Function settings (for indoor unit)
FIELD
WORKING
FIELD
WORKING
Содержание ABHG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Страница 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Страница 62: ......
Страница 212: ...9 17 Model AOHG36KBTA5 02 150 9 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Страница 216: ......
Страница 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Страница 320: ......
Страница 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...