03-01
3-1. FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
3-1-1 INDOOR UNIT
( Factory setting)
1-2. Setting the Ceiling height (For AU, AB type)
Setting Description
Function Number
Setting Value
Standard (Max 3.2m)
High ceiling
(30:Max 3.6m, 36:Max 4.2m)
20
00
01
Low ceiling (Max 2.7m)
02
The ceiling height values are for the 4 way outlet.
Do not change this setting in the 3 way outlet mode.
Determine the wind volume in each mode.
Select the setting values in the table below according to the height of the ceiling.
( Factory setting)
Setting Description
Function Number
Setting Value
Standard (2,500 hours)
Long interval (4,400 hours)
Short interval (1,250 hours)
No indication
11
00
01
02
03
1-1. Setting the Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter.
Select the time setting for the filter sign display interval in the table below according to
the amount of dust or debris in the room.
If you do not wish the filter sign to be displayed, select the setting value for "No indication".
( Factory setting)
Setting Description
Function Number
Setting Value
Normal
High static pressure 1
High static pressure 1
High static pressure 1
21
00
01
02
03
1-3. Static pressure (For AR type)
Select appropriate static pressure according to the installation conditions.
[AU type]
( Factory setting)
Setting Description
Function Number
Setting Value
Standard (2.5~3.0m)
High ceiling
(3.0m or more)
20
00
01
[AB type]
Содержание AB*G30LRTE series
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Страница 26: ......
Страница 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Страница 62: ......
Страница 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Страница 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...