The indoor fan motor will run as shown in Fig. 6.
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.6.
It depends on the Function setting "Indoor unit fan control for energy saving".
8. INDOOR UNIT FAN (CONTROL FOR ENERGY SAVING (Cooling mode))
When the defrost operation starts, the indoor fan runs according to cool air prevention control for 20 seconds.
And the fan is stopped if 20 seconds have passed.
When 60 seconds have passed after defrost operation is released,
the fan runs according to cool air prevention control
9. DEFROST OPERATION
( Fig. 6 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 5)
S-Lo
OFF
10
30
60
180
60
180
60
10
30
(SEC)
( Table 5 : Indoor fan speed )
AU*G30/ 36LRLE
420 rpm
420 rpm
AR*G30/ 36LMLE
630 rpm
630 rpm
AB*G30/ 36LRTE
650 rpm
650 rpm
Dry
Cooling