The airflow can be switched in 5 steps such as AUTO, Quiet, Low, Med, High,
while the indoor fan only runs.
When Fan mode is set at [AUTO], it operates on [Med] Fan Speed.
01-05
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 3.
On the other hand, if switched in [High] ~ [Quiet], the indoor motor will run at a constant airflow of [COOL]
operation modes Quiet, Low, Med, High, as shown in Table 4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
High mode
Med mode
Low mode
4. DRY OPERATION
Refer to the Table 4.
During the dry mode operation, the fan speed setting can not be changed.
=
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 4.
On the other hand, if switched in [High] ~ [Quiet], the indoor motor will run at a constant airflow
of [HEAT] operation modes Quiet, Low, Med, High, as shown in Table 4.
( Fig. 4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Low mode
Med mode
High mode
Содержание AB*G30LRTE series
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Страница 26: ......
Страница 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Страница 62: ......
Страница 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Страница 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...