Trouble shooting 15
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
16.1
5
20.7
26.9
35.2
46.6
62.3
115.2
Resistance value (k )
0
-5
-10
-20
224.3
-30
Temperature (°C )
10
15
1.6
2.4
3.5
5.2
8.0
Resistance value (k )
70
1.2
80
60
50
40
30
12.6
20
Temperature (°C )
Outdoor Thermistor Error
Outdoor unit Main PCB
Outdoor temperature thermistor
When Outdoor temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-17
Refer to error code table.
OK
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
BROWN
BROWN
Thermistor
(Discharge pipe)
Thermistor
(Heat exchanger)
Thermistor
(Outdoor temp.)
Thermistor
(Compressor temp.)
3
2
1
3
2
1
CN64
BLUE
BLUE
3
2
1
3
2
1
CN62
BLACK
BLACK
3
2
1
3
2
1
CN65
BROWN
BROWN
3
2
1
3
2
1
CN63
Содержание AB*G30LRTE series
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Страница 26: ......
Страница 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Страница 62: ......
Страница 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Страница 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...