Trouble shooting 2
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YES
YES
NO
OK
Serial Communication Error
(Serial Forward Transfer Error)
Indoor unit Controller PCB
Indoor unit Fan motor
Outdoor unit Main PCB
1. Connection failure 2. External cause 3. Controller PCB failure 4. Indoor unit fan motor failure
5. Outdoor unit Main PCB
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 :
Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC216V(AC240V-10%) - 264V(10%) appears
at outdoor unit terminal L - N.
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC30V and AC130V at outdoor unit terminal 2 - 3.
>> If it is abnormal, replace Controller PCB.
>> If it is abnormal, Check Indoor unit fan motor. (PARTS INFORMATION 4)
>> If Indoor unit fan motor is abnormal, replace Indoor unit fan motor and Controller PCB.
>> If it is abnormal, replace Outdoor unit Main PCB.
When the outdoor unit cannot properly receive the serial signal from
indoor unit for 10 seconds or more.
02-04
1
2
3
L
N
RED
WHITE
BLACK
BLACK
WHITE
+
-
Содержание AB*G30LRTE series
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Страница 26: ......
Страница 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Страница 62: ......
Страница 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Страница 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...