Trouble shooting 12
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
17.8
26.3
20
40.0
62.5
79.1
100.9
129.8
168.6
Resistance value (k )
15
10
1013.1
-30
531.6
-20
292.9
-10
221.1
-5
5
0
Temperature (°C )
12.3
30
50
40
60
2.0
3.4
4.6
6.3
8.7
Resistance value (k )
120
100
90
80
70
Temperature (°C )
Discharge Thermistor Error
Outdoor unit Main PCB
Discharge pipe temperature thermistor
When Discharge pipe temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-14
Refer to error code table.
BROWN
BROWN
Thermistor
(Discharge pipe)
Thermistor
(Heat exchanger)
Thermistor
(Outdoor temp.)
Thermistor
(Compressor temp.)
3
2
1
3
2
1
CN64
BLUE
BLUE
3
2
1
3
2
1
CN62
BLACK
BLACK
3
2
1
3
2
1
CN65
BROWN
BROWN
3
2
1
3
2
1
CN63
Содержание AB*G30LRTE series
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Страница 26: ......
Страница 27: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Страница 62: ......
Страница 63: ...3 APPENDING DATA R410A Cassette Duct Ceiling type INVERTER ...
Страница 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2013 Printed in Japan ...