4. AUTO CHANGEOVER OPERATION
01-03
Operation flow chart
START
Room temp.
Room temp.
>Ts+2°C ?
COOLING OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
NO
YES
YES
T
S
:
Setting temperature
<Ts- 2°C ?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
YES
YES
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1°C steps.