OUT1 Range
,
OUT2 Range
Specifies the range for control output (OUT1/OUT2)
• Range
0-5
: 0V to 5V
1-5
: 1V to 5V
0-10 : 0mA to 10V
2-10 : 2V to 10V
0-20 : 0mA to 20mA
4-20 : 4mA to 20mA
Setting the OUT1/OUT2 Range
The following steps explain how to set OUT1 range by using
0mA to 20mA as an example.
Caution
Do not use 0-5, 1-5, 0-10, or 2-10 if current is selected for output 1
and output 2 in the model specifications. Do not use 0-20 or 4-20
if voltage is selected for output 1 and output 2.
The unit will not operate properly if improper settings are
chosen.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to select C1r ("
CCC
C1111rrrr
").
3
Press the
key, then use the
keys to
select 0-20 when the bottom part of the display
begins to blink.
The OUT1 range is set to 0mA to 20mA.
4
Press the
key to confirm the setting.
5
Repeat steps 2-4 (excluding pressing and holding
the
key) to set FALT OUT2.
6
Press the
key to return to the operation
mode PV/SV display.
FALT OUT1 Value
,
FALT OUT2 Value
This is the procedure for specifying the output value of
OUT1/OUT2 should this device fall go into the FALT state
(Input Error).
• Range: -3.0% to 103.0% (OUT1/OUT2)
Setting FALT OUT1/OUT2
The following steps explain how to set the FALT OUT1/OUT2
setting by using 5% as an example.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to select Flo1 ("
FFF
Flllloooo1111
").
3
Press the
key, then use the
keys to
select 5.0 when the bottom part of the display
begins to blink.
OUT1 output is set to 5.0%.
4
Press the
key to confirm the setting.
5
Repeat steps 2-4 (excluding pressing and holding
the
key) to set FALT OUT2.
6
Press the
key to return to the operation
mode PV/SV display.
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...