![FujiFilm PXG4 Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483056.webp)
– 55 –
6
Chapter
Note 1: Turn off the power to the unit after changing the parameters with [RST] in the remarks column.
Note 2: The range of the parameters in the shaded area indicates the industrial values.
Note 3: Do not change this parameter during ramp/soak operations. Make sure that
"
PrG
"
=
"
oFF
"
before making changes.
"
MMM
Moooodddd
" (Mod)
Ramp/soak mode
Sets the program
operation method
0
(P-ON: Off, End: Maintain,
OFF: Maintain, Repeat: Off)
1
(P-ON: Off, End: Maintain,
OFF: Maintain, Repeat: On)
2
(P-ON: Off, End: Maintain,
OFF: Standby, Repeat: Off)
3
(P-ON: Off, End: Maintain,
OFF: Standby, Repeat: On)
4
(P-ON: Off, END: Standby,
OFF: Maintain, Repeat: Off)
5
(P-ON: Off, END: Standby,
OFF: Maintain, Repeat: On)
6
(P-ON: Off, END: Standby,
OFF: Standby, Repeat: Off)
7
(P-ON: Off, END: Standby,
OFF: Standby, Repeat: On)
8
(P-ON: On, End: Maintain,
OFF: Maintain, Repeat: Off)
9
(P-ON: On, End: Maintain,
OFF: Maintain, Repeat: On)
10 (P-ON: On, End: Maintain,
OFF: Standby, Repeat: Off)
11 (P-ON: On, End: Maintain,
OFF: Standby, Repeat: On)
12 (P-ON: On, END: Standby,
OFF: Maintain, Repeat: Off)
13 (P-ON: On, END: Standby,
OFF: Maintain, Repeat: On)
14 (P-ON: On, END: Standby,
OFF: Standby, Repeat: Off)
15 (P-ON: On, END: Standby,
OFF: Standby, Repeat: On)
0
59
"
GGG
Gssssooookkkk
" (GSok)
Guaranty soak
ON/OFF
Sets the guaranty soak on
or off.
oFF(guaranty soak off)
on (guaranty soak on)
oFF
60
"
GGG
GSSSS----LLLL
" (GS-L)
Guaranty soak band
(lower)
Sets the lower limit for the
guaranty soak band
0% to 50% FS
5°C
60
"
GGG
GSSSS----hhhh
" (GS-h)
Guaranty soak band
(upper)
Sets the upper limit for the
guaranty soak band.
0% to 50% FS
5°C
"
PPP
PvvvvSSSSTTTT
"(PvST)
PV start
Sets whether or not to
start ramp soak with PV.
oFF (PV start off)
on (PV start on)
oFF
61
"
CCC
CoooonnnnTTTT
"(ConT)
Continue mode
Sets how to restart when
the controller is restored
after a power loss during
ramp soak.
rES (Reset)
Con (Continue)
ini (Restart)
rES
(Note 3)
61
"
PPP
PTTTTnnnnMMMM
" (PTnM)
Sets the max pattern
selection
Choosing pattern with the
user key sets it to the
maximum possible
number.
0 to 6, di
6
62
"
PPP
PMMMMiiiinnnn
"(PMin)
Pattern selection Min
setting
Choosing pattern with the
user key sets it to the
minimum possible
number.
0 to 6, di
0
62
Display
Parameter name
Function
Setting range
Initial value
Remarks
Page
RST
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...