![FujiFilm PXG4 Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483037.webp)
– 36 –
4
Chapter
Anti-reset Windup
Anti-reset windup is a function that limits the range of
valid integration to control overshooting.
• Range Ar
: 0% to 100% FS
●
The anti-reset windup function ("
AAA
Arrrr
") cuts integration that
falls outside of the Ar set range that is centered around SV.
It is automatically set to the optimum value when auto-
tuning is activated.
Setting the Anti-reset Windup
Caution
This controller implements fuzzy control. With fuzzy control,
overshoot is minimized even if “bAL” and “Ar” are not used.
PV
SV
}
}
}
AR value
This range of integration
is cut.
This range is integrated.
This range of integration
is cut.
t
AR value
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display Pid ("
PPP
Piiiidddd CCCChhhh 2222
").
Refer to
See p. 31 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key to display P ("
PPP
P
") then
use the
keys to display Ar ("
AAA
Arrrr
").
Set the anti-reset windup value.
3
Press the SEL key, then use the
keys to
set anti-reset windup value to "500".
The anti-reset windup value is set to "500°C".
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation mode
PV/SV display.
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...