– 75 –
8
Chapter
PV Input Lower Limit
,
PV Input Upper Limit
This is the procedure for specifying the upper and lower
limits of PV input. PV input can be set to any value within
these bounds.
• Range: -1999% to 9999%
Setting PV Input Upper/Lower Limits
The following steps explain how to set PV input limits by using an
upper limit of 1000°C and a lower limit of 200°C as an example.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to display Pvb ("
PPP
Pvvvvbbbb
").
3
Press the
key, then use the
keys to
select 200.0 when the bottom part of the display
begins to blink.
The PV input lower limit is set to 200°C.
4
Press the
key to confirm the setting.
5
Repeat steps 2-4 (excluding pressing and holding
the
key) to set the PV input upper limit PvF
("
PPP
PvvvvFFFF
") to 1000°C.
6
Press the
key to return to the operation
mode PV/SV display.
Caution
The value for each sensor can be set to exceed the possible
measurement range, but accuracy is not guaranteed in these
cases.
PV input
1200
°
C
0
°
C
1000
°
C
200
°
C
Possible range for
setting upper/lower limit
Decimal Place
This is the procedure for setting the decimal place in the
PV display.
• Range
0: No decimal place
1: One decimal place
2: Two decimal places
Setting the Decimal Place
The following steps explain how to set the decimal place by
using one decimal place as an example.
Point
• Two decimal places are available only when the input is
voltage/current.
• When using one decimal place display for temperature
input, the decimal place will not be displayed for
temperatures of 1000°C and over.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to display Pvd ("
PPP
Pvvvvdddd
").
3
Press the
key, then use the
keys to
select 1 when the bottom part of the display begins
to blink.
The decimal place is now set to one decimal place.
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation mode
PV/SV display.
one decimal place
two decimal places
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...