– 44 –
5
Chapter
Overview of PID Palette Parameters (Ch3)
This function records SV and control parameters such as PID. Any of the up to 7 sets stored can be easily recalled by
using their number.
This is very useful when operating conditions change frequently.
The palette menu (ch3) consists of the following function blocks.:
Refer to
To change the SV No. or PID No., refer to "SV No. Switch" (page 26), "Changing PID No." (page 27), or "DI Function Select" (page 94).
Display
Parameter name
Function
Setting range
Initial value
Remarks
Page
"
Sv1
" (Sv1)
SV set value 1
Sets the SV value
SV lower limit (SVL) to SV upper limit
(SVH) %FS
0%FS
Note 1
46
"
P1
" (P1)
Proportional band 1
Sets the proportional band
0.0% to 999.9%
5.0%
47
"
i1
" (i1)
Integration time 1
Sets the integration time
0 sec to 3200 sec
240 sec
47
"
d1
" (d1)
Derivative time 1
Sets the derivative time
0.0 sec to 999.9 sec
60.0 sec
47
"
hyS1
" (hyS1)
ON/OFF Control
Hysteresis 1
Sets the hysteresis when
using ON/OFF control
0% to 50% FS
1°C
48
"
CoL1
" (CoL1)
Cooling proportional
band 1
Sets the cooling proportional
band
0.0 to 100.0
1.0
Note 2
48
"
db1
" (db1)
Dead band 1
Sets the dead band
-50.0% to 50.0% FS
0%
Note 2
49
"
bAL1
" (bAL1)
Output convergence
value 1
Offset value added to the
control output
-100.0% to 100.0% FS
0/50
(single/dual)
49
"
Ar1
" (Ar1)
Anti-reset windup 1
Sets the anti-reset windup
0% to 100% FS
100%FS
50
"
rEv1
" (rEv1)
Normal/reverse
setting 1
Sets the control output to
normal or reverse
rv-- (heat (reverse) / cool (none))
no-- (heat (normal) / cool (none))
rvno (heat (reverse) / cool (normal))
norv (heat (normal) / cool (reverse))
rvrv (heat (reverse) / cool (reverse))
nono (heat (normal) / cool (normal))
rv--/rvno
(single/dual)
Note 3
50
"
Sv7
" (Sv7)
SV set value 7
Sets the SV value
SV lower limit (SVL) to SV upper limit
(SVH) %FS
0%FS
Note 1
46
"
P7
" (P7)
Proportional band 7
Sets the proportional band
0.0% to 999.9%
5.0%
47
"
i7
" (i7)
Integration time 7
Sets the integration time
0 sec to 3200 sec
240 sec
47
• Proportional band
• Integration time
• Derivative time
• ON/OFF control hysteresis
• Cooling proportional band
• Dead band
• Output convergence value
• Anti-reset windup
• Normal/reverse setting
PID
Palette 7
Palette 6
Palette 5
Palette 4
Palette 3
Palette 2
Palette 1
Maximum SV selection number
Maximum PID selection number
Set Value (SV)
PID Palette Function Block
RST
...
...
...
...
...
...
...
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...