– 38 –
4
Chapter
SV Lower Limits
,
SV Upper Limits
These settings specify the range to which SV can be set.
SV can be set to any value in the measurement range.
• Range: 0% to 100% FS (lower/upper limit)
The relationship between SV limits and the measurement
range is as follows:
Setting the SV Upper and Lower Limits
Caution
• Set the lower and upper SV limits only after setting the
following parameters in the setup menu.
PV Input Upper Limit ("
Pvb
") /Lower Limit ("
PvF
")
• SVs set before setting the SV limits (Local SV, Palette SV,
etc.) are affected by new SV limits.
• Make sure to set the value of SVh greater than SVL.
set value
PV input
upper limit
PV input
lower limit
SV upper limit
PV input range
SV lower limit
(upper limit > lower limit)
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display Pid ("
PPP
Piiiidddd CCCChhhh 2222
").
Refer to
See p. 31 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key to display P ("
PPP
P
"), then
use the
keys to display SvL ("
SSS
SvvvvLLLL
").
Specify the PV lower limit.
3
Press the
key, then use the
keys to set
the normal/reverse settings to "50" when the bottom
part of the display begins to blink.
The SV lower limit is set to 50°C.
4
Press the
key to confirm the setting.
5
Repeat steps 2-4 (excluding pressing and holding
the
key) to set the SV upper limit.
6
Press the
key to return to the operation mode
PV/SV display.
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...